All Long Island districts
Nassau County, NY·PWSID NY2902851

Roslyn WD

Public water district serving Roslyn · approximately 17,000 residents.

Email delivery

Submitting a DOH-1013

Receives submissions by email.

Roslyn WD currently accepts DOH-1013 backflow test submissions by email. Potaflow can deliver your test on your behalf with a timestamped delivery record.

District rules

Backflow testing in Roslyn WD

What Roslyn WD publishes about backflow testing, from its own website.

Areas served

The Villages of Roslyn, Roslyn Estates and East Hills, and parts of Roslyn Heights, Roslyn Harbor, Flower Hill, North Hills, Greenvale, Albertson, Glenwood Landing and Port Washington.

Who must test
  • Every owner of a premises with a backflow device, under the district ordinance (Section 10.3).
  • Every new service connection gets a double check valve or a reduced pressure zone (RPZ) device, as the district decides.
  • Existing services need a device where they feed an irrigation system or a solar heating system, or a non-residential building the district finds needs one.
  • Every underground sprinkler system needs a double check valve.
How often
  • Every year, by a NYS DOH certified tester.
  • A device that fails must be repaired and retested within 30 days.
When reports are due

The DOH-1013 goes to the NYS Health Department, the Nassau County Health Department and the district within 30 days of the test.

How reports are filed

The district asks for all backflow testing documents by email.

Who can test
  • A NYS DOH certified backflow tester.
  • Each device carries a tag with the inspection date and the name and address of whoever did it.
New devices
  • Before installation, a DOH-347 application with plans by a NYS licensed engineer or registered architect needs approval from the district and the Nassau County Department of Health.
  • The owner's licensed plumber installs the device, certifies it was installed to plan, and reports the first test within 30 days.
  • The district inspects the finished installation.
  • New fire sprinkler systems need at least a double check detector assembly.
Lawn sprinkler systems
  • A new or changed system needs a district permit application with plans.
  • The double check valve goes directly after the meter, in the meter pit if there is one, and inside the home only with district and Nassau County Health Department approval.
  • After installation the owner furnishes a DOH-1013 showing the device was tested, and the district inspects the device and the rain sensor.
Questions

District office, (516) 621-7770, 6:30 AM to 3:00 PM, 24 West Shore Road, Roslyn.

Checked Nov 19, 2026 on the district's website: Backflow compliance, Rules and regulations, Downloadable forms, Ordinance (PDF). Rules can change, so confirm a date with the district before you rely on it.

About this district

System characteristics

Population served
17,000
Water source
Groundwater
PWSID
NY2902851
County
Nassau County, NY

Wholesale relationship

Roslyn WD receives wholesale water from Glenwood WD, as recorded by NYS DEC.

A note from the district

Submissions are processed within 3-5 business days.

Nearby

Other districts in Nassau County

District details sourced from NYS DEC Public Water Supply Service Areas and NYS DOH Public Water System Contact Reports. If you represent Roslyn WD and notice an error, please let us know.